Ballast box installation for anti-glare emergency lights

Determine the installation position of the lamp and power box, select the appropriate installation method, and prepare the corresponding length of Φ8 three-core cable and Φ10 five-core cable.

According to the installation requirements, the lamp and the ballast box are respectively fixed and fixed, and the two cover opening buttons at the bottom of the lamp head are pressed by hand, the front cover of the lamp is opened, and the foam fixing the lamp bulb is taken out. Then insert one end of the three-core cable through the Golan connector to introduce the lamp. Tighten the nut to prevent the cable from loosening. Connect the live wire according to the letter “L” next to the lamp socket, “N” the neutral wire, and the ground symbol ground wire. Then buckle the front cover.

Use a M5 Allen key to open the ballast box cover and remove the electronic ballast board. The other end of the three-core cable connected to the luminaire is introduced into the output end of the ballast box, and the cable is respectively connected to the "L", "N" and grounding terminals of the output of the electronic ballast board, and then the five-core cable is The input device introduces the ballast box, and the three wires with thicker wire diameters are respectively connected to the input “L”, “N” and the ground terminal of the electronic ballast board, and the fine yellow and green wires are connected to the electronic ballast. The "yellow" and "green" control lines of the board.

Insert the black wire of the battery placed in the ballast box into the negative terminal of the battery on the electronic ballast board, then install the electronic ballast into the box and fix it.

Pulling the emergency function switch of the ballast circuit board to the OFF position can realize the external line control emergency function of the lamp.

Connect the fine yellow and green signal wires of the five-core cable directly to a switch that controls the emergency power supply. Connect the thicker three wires to the live, neutral and ground wires of the mains to achieve lighting.

Rubber Tape Measure

At present, Liang metalworking Tools Co., Ltd. has more than 200 employees, who have undergone professional technical training and rich production technology experience. The company has self-supporting import and export rights, and more than 90% of its products are exported to Italy, More than 60 countries and regions, including Spain, the Netherlands, Poland, Russia, Nigeria, India, Iran, South Africa, Japan, Brazil, ELDOR, etc